PHS-864A Non-contact Phase Sequence Detector is suitable for live line tracing, simple electrical inspection, missing phase determination, and fault location detection. Its measurement principle is electrostatic induction, suitable for cables with an outer diameter of Φ10mm to 40mm. No need for wire stripping or contacting high voltage, it is safe and convenient to operate.
Measurement Specification
Measurement Principle : Electrostatic Induction
Input Voltage : 70~1000VAC
Frequency Range : 45~65Hz
Applicable
Wire Diameter : Φ10mm~40mm
Automatic Shut-off : Approx. five minutes
Low Battery Warning : LED Indicator
Power Supply : AA Alkaline Batteries x 2
Battery Life : Approx. 70 hours
Operating Temperature and Humidity : 0℃~40℃, Max Relative Humidity 80%
Storage Temperature and Humidity : -10℃~50℃, Max Relative Humidity 80%
Test Cable Length : Approx. 60cm
Dimensions : 70(L) x 75(W) x 30(H) mm
Weight (with batteries) : Approx. 200g
Accessories : Manual, Case, Batteries